Breaker Question - 20 Amp Breaker, 14 wire

I recently purchased a house, and it is clear that the previous owner had not always done things correctly. My present concern is that there seems to be 14 gauge wire running off a 20 AMP breaker. I believe this is a code violation, and more importantly a fire risk. I would rather not open up the walls to replace the wire. Assuming the circuit would be OK on a 15, can I just have the breaker replaced? Is that an adequate solution?

Thanks,

Concerned

Ad
Showing: Answers Sort: Relevance
Best Answer

Yes, that is a code violation and a fire risk.

And it invalidates the insurance.

To fix the problem,

1) get a breaker from the same brand and series but with a 15 Amp rating

2) turn the 20 Amp breaker off and pull it out.

3) swap the wire, that goes to it, over to the 15 Amp breaker

4) Make sure the 15 Amp breaker is turned OFF

5) insert the 15 Amp breaker

6) make sure the 15 Amp breaker is inserted fully and looks level with the other breakers

7) turn the 15 Amp breaker on and test the appliances or outlets that are fed from it.

If you forget point 4), there will be scary sounding arcing and sparking that could startle you into falling off your ladder or chair.

Have FUN!

DearWebby

http://www.webby.com/humor/

Ad
ReplyWas this helpful?Helpful? Yes

I have a similar question. In a recently purchased home, I have realized that all my 15 amp outlets and light switches etc. and pretty much everything else for that matter, seems to running off of 20 amp breakers. I don't know how to tell what size the wires are. Are the 20 amp breakers cause for concern?

ReplyWas this helpful?Helpful? Yes

Yes, that definitely would be cause for major concern.

A 20 Amp breaker does not adequately protect a 15 Amp outlet.

The breaker is supposed to pop instead of, or before the house burns down.

Even in the very unlikely event that you have 20 Amp wiring, the appliances plugged into the 15 Amp outlet need to be protected with 15 Amp breakers.

Your fire insurance would not have to pay in case of a fire, since your house is not up to code. It would be a good idea to get an electrical inspector or experienced electrician to check out your house and tell you what needs to be done to bring it up to code.

Have FUN!

DearWebby

http://www.webby.com/humor/

ReplyWas this helpful?Helpful? Yes

Hi , my breakers are all of 10 amps, I need to hook up an amplifier with a recommended current supply of 20 amp, can I simply replace the rooms breaker into a 20 amps or do I need to replace the whole wiring system in this room ?

Thanks

ReplyWas this helpful?Helpful? Yes

"Eliav GovAri (Guest Post) 2005-07-30

Hi , my breakers are all of 10 amps, I need to hook up an amplifier with a recommended current supply of 20 amp, can I simply replace the rooms breaker into a 20 amps or do I need to replace the whole wiring system in this room ?

Thanks "

Eliav, if you use bigger breakers than what the wires are rated for, then you are invalidating your insurance. They will not pay, only laugh, if you have a fire.

You most definitely need 20 Amp rated wiring FIRST, and a 20 Amp breaker after the wiring has been installed or upgraded.

If you put a 20 Amp breaker onto 15 Amp wiring, then you might as well replace the breaker with solid wire.

There is no cheap alternative. You have to upgrade the wiring, either after the fire, or instead of a fire.

Have FUN

DearWebby

http://webby.com/humor

ReplyWas this helpful?Helpful? Yes

I have 1 1/2 HP pool pump wired for 115, No. 10 gage wired to a 15 amp breaker used for a 24/7 waterfall. Manufacturer recommends 30 amp breaker. The pump can be wired for 230 using a 15 amp breaker if the wire is upgraded to 14 gage. Two questions: Is there a cost benefit in KW usage to upgrade to 230 and if there is no KW benefit could the 15 amp breaker just be upgraded to 30 amp breaker to end the breaker tripping?

ReplyWas this helpful?Helpful? Yes

The National electric code book for 2008 says that for 20 amp branch circuits there must be 12 gage wire but the receptacle rating can be of 15 or 20 amp rating, in a residential situation only. In a business or school situation, most branch circuits are 20 amps and the NEC says they must be 20 amp receptacles installed. The most common way to tell if a receptacle is rated for 20 amps is the wider blade neutral slot will have a sideways slot off to the side of it. These plugins are rarely seen in residential situations.

ReplyWas this helpful?Helpful? Yes

I'm glad I found this forum and I'm also glad I have an electrician coming this afternoon to check things out. If you don't know what you're doing, get someone who does.

ReplyWas this helpful?Helpful? Yes

Do not ever hookup or put things that you have to think twice about. If you know for positive, then hook it up! Everything electrical has a code! If you want it done right, and no! You can not put 20amp breakers where 15amp breakers go! For some that do not no 20amp breaker is rated for #12 wire only, and a 15amp breaker is rated #14 wire.tip:(home depot) has books on electrical and codes and you can look it up for free!

ReplyWas this helpful?Helpful? Yes
Ad
Answer

In This Article
Electrician Working on Circuit Breakers
Troubleshooting Circuit Breaker Problems
Categories
Home and Garden Home Improvement Lighting and ElectricFebruary 2, 2005
More to Explore
ThriftyFun on Facebook
ThriftyFun on Pinterest
Enter a Contest
Free Newsletters
Ask a Question
Share a Post
Related Guides
Outdoor Wire Reindeer
Reusing Outdoor Wire Christmas Decorations
Bailing Wire
Craft Ideas Using Baling Wire
man working on breaker box
Replacing a 200 Amp Breaker Box
changing an outlet
Changing a 15 Amp Outlet to 20 Amps
© 1997-2016 by Cumuli, Inc. All Rights Reserved. Published by . Page generated on May 3, 2016 at 7:13:05 AM on 10.0.1.158 in 354 msecs. Use of this web site constitutes acceptance of ThriftyFun's Disclaimer and Privacy Policy. If you have any problems or suggestions feel free to Contact Us.
 
To Top
Loading Something Awesome!